COMMERCIAL LAWS SUPPLEMENT
(b) All inner courts shall be connected to a street or yard,
either by a passageway with a minimum width of 1.20
meters or by a door through a room or rooms.
SECTION 805. Ceiling Heights . — (a) Habitable rooms
provided with artificial ventilation have ceiling heights
not less than 2.40 meters measured from the floor to the
ceiling;
Provided,
that
for
buildings
of
more
than
one-storey, the minimum ceiling height of the first storey
shall be 2.70 meters and that for the second storey 2.40
meters
and
succeeding
storeys
shall
have
an
unobstructed typical head-room clearance of not less
than 2.10 meters above the finished floor. Above stated
rooms with a natural ventilation shall have ceiling height
not less than 2.70 meters.
(b) Mezzanine floors shall have a clear ceiling height not
less than 1.80 meters above and below it.
SECTION 806. Size and Dimensions of Rooms .— (a)
Minimum
sizes
of
rooms
and
their
least horizontal
dimensions shall be as follows:
1. Rooms for Human Habitations — 6.00 square meters
with at least dimensions of 2.00
2. Kitchens — 3.00 square meters with at least dimension
of 1.50 meters;
3. Bath and toilet — 1.20 square meters with at least
dimension of 0.90 meters.
SECTION 807. Air Space Requirements in Determining
the Size of Rooms . — (a) Minimum air space shall be
provided as follows:
1. School Rooms — 3.00 cubic meters with 1.00 square
meter of floor area per person;
2. Workshops, Factories, and Offices — 12.00 cubic meters
of air space per person;
3. Habitable rooms — 14.00 cubic meters of air space per
person.
SECTION 808. Window Openings . — (a) Every room
intended
for
any
use,
not
provided
with
artificial
ventilation system as herein specified in this Code, shall
be provided with a window or windows with a total free
area of openings equal to at least ten percent of the floor
area of room, and such window shall open directly to a
court, yard, public street or alley, or open water courses.
SECTION 809. Vent Shafts . — (a) Ventilation or vent shafts
shall have a horizontal cross-sectional area of not less
than 0.10 square meter for every meter of height of shaft
but in no case shall the area be less than 1.00 square
meter. No vent shaft shall have its least dimension less
than 600 millimeters.
(b) Skylights — Unless open to the outer air at the top for
its full area, vent shaft shall be covered by a skylight
having a net free area or fixed louver openings equal to
the maximum required shaft area.
(c) Air ducts shall open to a street or court by a horizontal
duct or intake at a point below the lowest window
opening. Such duct or intake shall have a minimum
unobstructed cross-sectional area of not less than 0.30
square
meter
with
a
minimum
dimension
of
300
millimeters. The openings to the duct or intake shall not
be less than 300 millimeters above the bottom of the
shaft and the street surface or level of court at the
respective ends of the duct or intake.
SECTION 810. Ventilation Skylights . — (a) Skylights shall
have glass area not less than that required for the
windows that are replaced. They shall be equipped with
movable sashes or louvers with an aggregate net free
area not less than that required for openable parts in the
window that are replaced or provided with approved
artificial ventilation of equivalent effectiveness.
SECTION 811. Artificial Ventilation . — (a) Rooms or spaces
housing
industrial
or
heating
equipment
shall
be
provided with artificial means of ventilation to prevent
excessive accumulation of hot and/or polluted air;
(b)
Whenever
artificial
ventilation
is
required,
the
equipment shall be designed and constructed to meet
the following minimum requirements in air changes:
1. For rooms entirely above grade and used for office,
clerical, or administrative purposes, or as stores, sales
rooms,
restaurants,
markets,
factories,
workshops, or
machinery rooms, not less than three changes of air per
hour shall be provided.
2. For rooms entirely above grade and used as bakeries,
hotel
or
restaurant
kitchens,
laundries
other
than
accessory to dwellings, and boiler rooms — not less than
ten changes of air per hour shall be provided.
3. For auditorium and other rooms used for assembly
purposes, with seats or other accommodations — not less
than 0.03 cubic meter of air per minute shall be supplied
for each person.
4. For wards and dormitories of institutional buildings —
not less than 0.45 cubic meter of air per minute shall be
supplied for each person accommodated.
5. For other rooms or spaces not specifically covered
under this Section of the Code, applicable provisions of
the Philippine Mechanical Engineering Code, shall be
followed.
CHAPTER 9 Sanitation
SECTION 901. General . — Subject to the provisions of
Book II of the Civil Code of the Philippines on Property,
Ownership, and its Modification, all buildings hereafter
erected, altered, remodeled, relocated or repaired for
human habitation shall be provided with adequate and
potable water supply, plumbing installation, and suitable
wastewater treatment or disposal system, storm water
drainage, pest and vermin control, noise abatement
device,
and
such
other
measures
required
for
the
protection and promotion of health of persons occupying
the premises and other living nearby.
SECTION 902. Water Supply System . — (a) Whenever
available, the potable water requirements for a building
used
for
human
habitation
shall
be
supplied
from
existing municipal or city waterworks system.
(b) The quality of drinking water from meteoric, surface or
underground sources shall conform to the criteria set in
the
latest approved National Standards for Drinking
Water.
(c) The design, construction and operation of deepwells
for the abstraction of groundwater shall be subject to the
provisions of the Water Code of the Philippines .
(d)
The
design,
construction
and
operation
of
independent waterworks, systems of private housing
subdivisions or industrial estates shall be governed by
existing laws relating to local waterworks system.
(e) The water piping installations inside buildings and
premises shall conform to the provisions of the National
Plumbing Code of the Philippines.
SECTION
903.
Wastewater
Disposal
System .
—
(a)
Sanitary
sewage
from
buildings
and
neutralized
or
pre-treated industrial wastewater shall be discharged
directly into the nearest street sanitary sewer main of
existing municipal or city sanitary sewerage system in
accordance with the criteria set by the Code on Sanitation
and the National Pollution Control Commission.
(b) All buildings located in areas where there are no
available sanitary sewerage system shall dispose their
sewage "Imhoff" or septic tank and subsurface absorption
filled.
(c) Sanitary and industrial plumbing installations inside
buildings and premises shall conform to the provisions of
the National Plumbing Code.
SECTION 904. Storm Drainage System . — (a) Rain water
drainage shall not discharge to the sanitary sewer system.