shall extend from the ceiling downward at least 300
millimeters on all sides. Automatic sprinkles shall be
provided around the perimeter of the opening and within
a 600 millimeters of the draft curtain. The distance
between
the sprinkles shall not exceed 1.80 meters
center-to-center.
(c) Other Vertical Openings . — All shafts, ducts, chutes,
and other vertical openings not covered in paragraph (b)
above shall have enclosing walls conforming to the
requirements specified under the type of construction of
the building in which they are located. In other than
Group A Occupancies rubbish and linen chutes shall
terminate in rooms separated from the remainder of the
building
by
a
One-Hour
Fire-Resistive
Occupancy
Separation. Openings into the chutes shall not be located
in required exit corridors or stairways.
(d) Air Ducts . — Air ducts passing through a floor shall be
enclosed in a shaft. The shaft shall be as required in this
Code for vertical openings. Dampers shall be installed
where ducts pierce the shaft enclosure walls. Air ducts in
Group A Occupancies need not be enclosed in a shaft if
conforming to the mechanical provisions of this Code.
SECTION 1205. Floor Construction . — (a) Floors shall be of
such
materials
and
construction
as specified under
Chapter 5 — Fire Zones and Fire-Resistive Standards and
under Chapter 6 — Types of Construction.
(b) All floors shall be so framed and secure into the
framework and supporting walls as to form an integral
part of the whole building.
(c) The types of floor construction used shall provide
means
to
keep
the
beam and girders from lateral
buckling.
SECTION 1206. Roof Construction and Covering . — (a)
Roof Covering . — Roof covering for all buildings shall be
either fire-retardant or ordinary depending upon the
fire-resistive
requirements
of
the
particular
type
of
construction. The use of combustible roof insulation shall
be permitted in all types of construction provided it is
covered with approved roof covering applied directly
thereto.
(b) Roof Trusses . — All roofs shall be so framed and tied
into the framework and supporting walls so as to form an
integral part of the whole building. Roof trusses shall have
all joints well fitted and shall have all tension members
well tightened before any load is placed in the truss.
Diagonal and sway bracing shall be used to brace all roof
trusses. The allowable working stresses of materials in
trusses shall conform to this Code. Camber shall be
provided to prevent sagging.
(c) Attics — (1) Access . — An attic access opening shall be
provided in the ceiling of the top floor of buildings with a
combustible ceiling or roof construction. The opening
shall be located in a corridor or hallway of buildings of
three or more storeys in height, and readily accessible in
buildings of any height. An opening shall not be less than
600 millimeters square or 600 millimeters in diameter.
The minimum clear headroom of 800 millimeters shall be
provided
above
the
access
opening.
For
ladder
requirements,
refer
to
the
Philippine
Mechanical
Engineering Code.
(2)
Area
Separation .
—
Enclosed
attic
spaces
of
combustible construction shall be divided into horizontal
areas not exceeding 250 square meters by fire-resistive
partitions extending from the ceiling to the roof. Except ,
That where the entire attic is equipped with an approved
automatic fire-extinguishing system, the attic space may
be divided into areas not to exceed 750 square meters.
Openings
in
the
partitions
shall
be
protected
by
self-closing doors.
(3) Draft Stops . — Regardless of the type of construction,
draft stops shall be installed in trusses roofs, between roof
and bottom chords or trusses, in all buildings exceeding
2000 square meters. Draft stops shall be constructed as
for attic area separations.
(4) Ventilation . — Enclosed attics including rafter spaces
formed where ceilings are applied direct to the underside
or roof rafters, shall be provided with adequate ventilation
protected against the entrance of rain.
(d) Roof Drainage System .— (1) Roof Drains . — Roof drains
shall be installed at low points of the roof and shall be
adequate in size to discharge all tributary waters.
(2) Overflow Drains and Scuppers . — Where roof drains
are required, adequate overflow drains shall be provided.
(3) Concealed Piping . — Roof drains and overflow drains,
when concealed within the construction of the building,
shall be installed in accordance with the provisions of the
National Plumbing Code.
(4) Over Public Property . — Roof drainage water from a
building shall not be permitted to flow over public
property, except for Group A and J Occupancies.
(e) Flashing . — Flashing and counterflashing shall be
provided at the juncture of the roof and vertical surfaces.
SECTION 1207. Stairs, Exits and Occupant Loads . — (a)
General . — The construction of stairs and exits shall
conform to the occupant load requirements of buildings,
reviewing stands, bleachers and grandstands:
(1) Determinations of Occupant Loads . — The occupant
load permitted in any building or portion thereof shall be
determined by dividing the floor area assigned to that
use by the unit area allowed per occupant as determined
by the Secretary.
(2) Exit Requirements . — Exit requirements of a building
or portion thereof used for different purposes shall be
determined by the occupant load which gives the largest
number of persons. No obstruction shall be placed in the
required width of an exit except projections permitted by
this Code.
(3) Posting of Room Capacity . — Any room having an
occupant load of more than 50 where fixed seats are not
installed, and which is used for classroom, assembly, or
similar purpose shall have the capacity of the room
posted in a conspicuous place near the main exit from
the room.
(4)
Changes
in
Elevation .
—
Except
in
Groups
A
Occupancies, changes in floor elevations of less than 300
millimeters along any exit serving a tributary occupant
load of 10 or more shall be by means of ramps.
(b) Exits — (1) Number of Exits . — Every building or usable
portion
thereof
shall
have
at
least
one
exit.
In all
occupancies, floors above the first storey having an
occupant load of more than 10 shall not have less than
two exits. Each mezzanine floor used for other than
storage purposes, if greater in area than 185 square
meters or more than 18.00 meters in any dimension, shall
have at least than two stairways to an adjacent floor.
Every storey or portion thereof, having an occupant load
of 500 to 999 shall have at least three exits. Every storey or
portion thereof having an occupant load of 1000 or more
shall have at least four (4) exits. The number of exits
required
from
any
storey
of
a
building
shall
be
determined by using the occupant loads of floors which
exit through by using the occupant loads of floors which
exit through the level under consideration as follows: 50
percent of the occupant load in the first adjacent storey
above (and the first adjacent storey below, when a storey
below exits through the level under consideration) and 25
percent of the occupant load in the storey immediately
beyond the first adjacent storey. The maximum number
of exits required for any storey shall be maintained until
egress is provided from the structures. For purposes of
this Section basement or cellars and occupied roofs shall
be provided with exits as required for storeys. Floors
above the second storey, basements and cellars used for
other than service of the building shall have not less than
two exits.
(2) Width . — The total width of exits in meters shall not be
less than the total occupant load served divided by 165.
Such width of exits shall be divided approximately equally
among the separate exits. The total exit width required
© Compiled by RGL
120 of 203