COMMERCIAL LAWS SUPPLEMENT
load served. The required width of exit courts or exit
passageway shall be unobstructed except as permitted in
corridors. At any point where the width of an exit court is
reduced from any cause, the reduction in width shall be
affected gradually by a guardrail at least 900 millimeters
in height. The guardrail shall make an angle of not more
than 30 degrees with the axis of the exit court.
(2) Slope — The slope of exit courts shall not exceed 1 in 10.
The slope of exit passageway shall not exceed 1 in 8.
(3) Number of Exits — Every exit court shall be provided
with exits as required in this Code.
(4) Openings — All openings into an exit court less than
3.00 meters wide shall be protected by fire assemblies
having
not
less
than
three-fourth hour fire-resistive
rating. Except, that openings more than 3.00 meters
above the floor of the exit court may be unprotected.
(k)
Exit
Signs
and
Illuminations
—
Exits
shall
be
illuminated at any time the building is occupied with
light having an intensity of not less than 10.7 lux at floor
level: Except, that for Group A Occupancies, the exit
illumination shall be provided with separate circuits or
separated sources of power (but not necessarily separate
from exit signs when these are required for exit signs
illumination).
(1) Aisles — Every portion of every building in which are
installed seats, tables, merchandise, equipment, or similar
materials shall be provided with aisles leading to an exit.
(1) Width — Every aisles shall be not less than 800
millimeters wide if serving only one side, and not less
than 1 meter wide if serving both sides. Such minimum
width shall be measured at the point farthest from an
exit, cross aisle, or foyer and shall be increased by 30
millimeters for every meters in length towards the exit,
cross aisle or foyer.
(2) Exit Distance — In areas occupied by seats and in
Groups H and I Occupancies without seats, the line travel
to an exit door by an aisle shall be not more than 45.00
meters. With standard spacing, as specified in this Code,
aisles shall be so located that there will be not more than
seven seats between the wall and an aisle and not more
than fourteen seats between aisles. The number of seats
between aisle may be increased to 30 where exit doors
are provided along each side aisle of the row of seats at
the rate of one pair of exit doors for every five rows of
seats, provided further that the distance between seats
back to back is at least one meter. Such exit doors shall
provide a minimum clear width of 1.70 meters.
(3) Cross Aisles — Aisles shall terminate in a cross aisle,
foyer, or exit. The width of the cross aisle shall be not less
than the sum of the required width of the widest aisle
plus fifty percent of the total required width of the
remaining aisle leading thereto. In Groups C, H and E
Occupancies, aisle shall not be provided a dead end
greater than 6.00 meters in length.
(4) Vomitories —Vomitories connecting the foyer or main
exit with the cross aisles shall have a total width not less
than the sum of the required width of the widest aisles
leading thereto plus fifty percent of the total required
width of the remaining aisles leading thereto.
(5) Slope — The slope portion of aisle shall not exceed a
fall 1 in 8.
(m) Seats — (1) Seat Spacing — With standard seating, the
spacing of rows of seats from back-to-back shall not less
than
840
millimeters.
With
continental
seating, the
spacing of rows of unoccupied seat shall provide a clear
width measured horizontally, as follows: 450 millimeters
clear for rows of 18 seats or less; 500 millimeters clear for
rows of 35 seats or less; 525 millimeters clear for rows of 45
seats or less; and 550 millimeters clear for rows of 46 seats
or more.
(2) Width — The width if any seat be not less than 450
millimeters.
(n) Reviewing Stands, Grandstands, and Bleachers .— (1)
Height of Stands — Stands made of combustible framing
shall be limited to 11 rows or 2.70 meters in height.
(2) Design Requirements — the minimum unit live load
for reviewing stands, grandstands, and bleachers shall be
500 kilograms per square meter of horizontal projection
for the structure as a whole. Seat and footboards shall be
180 kilograms per linear meter. The sway force, applied to
seats, shall be 35 kilograms per linear meter parallel to the
seats and 15 kilograms per linear meter perpendicular to
the
seats.
Sway
forces
need
not
to
be
applied
simultaneously with other lateral forces.
(3) Spacing Seats — (3.1) Row spacing — The minimum
spacing of rows of seats measured from back-to-back
shall be: 600 millimeters for seats without backrests in
open air stands; 750 millimeters for seats with backrests,
and 850 millimeters for chair seating.
There shall be a space of not less than 300 millimeters
between the back of each seat and the front of the seat
immediately behind it.
(3.2) Rise Between Rows — The maximum rise from one
row of seats to the next shall not exceed 400 millimeters.
(3.3) Seating Capacity — For determining the seating
capacity of a stand the width of any seat shall not be less
than 450 millimeters nor more than 480 millimeters.
(3.4) Number of Seats Between Aisles — the number of
seats between any seat and an aisle shall not be greater
than 15 for open air stands with seats without backrests in
buildings.
(4) Aisles — (4.1) Aisles Required — Aisles shall be provided
in all stands: except, that aisles may be omitted when all
the
following
conditions
exists;
Seats
are
without
backrests; the rise from row to row does not exceed 300
millimeters per row; the number of rows does not exceed
11 in height; the top seating board is not over 3.00 meters
above grade; and the first seating board is not more than
500 millimeters above grade.
(4.2) Obstructions — obstruction shall be placed in the
required width of any aisle or exitway.
(4.3) Stairs Required — When an aisle is elevated more
than 200 millimeters above grade, the aisle shall be
provided with a stairway or ramp whose width is not less
than the width of the aisle.
(4.4) Dead End — No vertical aisle shall have a dead end
more than 16 rows in depth regardless of the number of
exits required.
(4.5) Width — Aisles shall have a minimum width of 1.10
meters.
(5) Stairs and Ramps — The requirements in this Code
shall apply to all stairs and ramps except for portions that
pass through the seating area.
(5.1) Stair Rise and Run — The maximum rise of treads
shall not exceed 200 millimeters and the minimum width
of the run shall be 280 millimeters. The maximum
variation in the width of treads in any one flight shall not
be more than 5 millimeters and the maximum variation
in one height of two adjacent rises shall not exceed 5
millimeters.
(5.2) Ramp Slope — The slope of a ramp shall not exceed 1
in 8. Ramps shall be roughened or shall be of approved
nonslip material.
(5.3) Handrails — A ramp with a slope exceeding 1 in 10
shall have handrails. Stairs for stands shall have handrails.
Handrails shall conform to the requirements of this Code.
(6) Guardrails — (6.1) Guardrails shall be required in all
locations where the top of a seat plank is more than 1.20
meters above the grade and at the front of stands
elevated more than 600 millimeters above grade. Where
only sections of stands are used, guardrails shall be
provided as required in this Code.
(6.2) Railings shall be 1.10 meters above the rear of a seat
plank or 1.10 meters above the rear of the steps in the aisle