COMMERCIAL LAWS SUPPLEMENT
SECTION 1210. Penthouses and Roof Structures . — (a)
Height — No penthouse or other projection above the
roof in structures of other than Type V construction shall
exceed 8.40 meters above the roof when used as an
enclosure for tanks or for elevators which run to the roof
and in all other cases shall not extend more than 3.60
meters in height with the roof.
(b) Area — The aggregate area of all penthouses and
other roof structures shall not exceed one third of the
area of the supporting roof.
(c) Prohibited Uses — No penthouse, bulkhead, or any
other similar projection above the roof shall be used for
purposes other than shelter of mechanical equipment or
shelter of vertical shaft openings in the roof. A penthouse
or bulkhead used for purposes other than that allowed by
this Section shall conform to the requirements of this
Code for an additional storey.
(d) Construction — Roof structures shall be constructed
with walls, floors, and roof as required for the main
portion of the building except in the following cases:
(1) On Types III and IV constructions, the exterior walls and
roofs of penthouses which are 1.50 meters or more from
an
adjacent
property
line
may
be
of
one-hour
fire-resistive non combustible construction.
(2) Walls not less than 1.50 meters from an exterior wall of
a type iv construction may be of one-hour fire-resistive
non combustible construction.
The above restriction shall not prohibit the placing of
wood flagpoles or similar structures on the roof of any
building.
(e) Towers and Spires — Towers and spires when enclosed
shall have exterior walls as required for the building to
which they attached. Towers not enclosed and which
extend more than 20.00 meters above the grade shall
have
their
framework
constructed
of
iron,
steel,
or
reinforced concrete. No tower or spire shall occupy more
than one-fourth of the street frontage of any building to
which it is attached and in no case shall the base area
exceed 150 square meters unless it conforms entirely to
the type of construction requirements of the building to
which it is attached and is limited in height as main part
of the building. If the area of the tower and spire exceeds
10.00 square meters any horizontal cross section, its
supporting frames shall extend directly to the ground.
The roof covering of the spires shall be as required for the
main room of the rest of the structure. Skeleton towers
used as radio masts, neon signs, or advertisement frames
and
placed
on
the
roof
of
any
building
shall
be
constructed entirely of incombustible materials when
more than 7.50 meters in height, and shall be directly
supported
on
an
incombustible
framework
to
the
ground. No such skeleton towers shall be supported on
roofs of combustible framings. They shall be designed to
withstand a wind load from any direction in addition to
any other loads.
SECTION 1211. Chimneys, Fireplaces, and Barbecues . — (a)
Chimneys — (1) Structural Design. — Chimneys shall be
designed, anchored, supported, reinforced, constructed,
and installed in accordance with generally accepted
principles of engineering. Every chimney shall be capable
of producing a draft at the appliance not less than that
required
for
the
safe
operation
of
the
appliance
connected
thereto.
No
Chimney
shall
support
any
structural load other than its own weight unless it is
designed to act as a supporting member. Chimneys in a
wood-framed building shall be anchored laterally at the
ceiling line and at each floor line which is more than 1.80
meters above grade, except when entirely within the
framework or when designed to be free standing.
(2) Walls — Every masonry chimney shall have walls of
masonry units, bricks, stones, listed masonry chimney
units, reinforced concrete or equivalent solid thickness of
hollow
masonry
and
lined
with
suitable
liners
in
accordance with the following requirements:
(2.1) Masonry Chimneys for Residential Type Appliances —
Masonry chimneys shall be constructed of masonry units
or reinforced concrete with walls not less than 100
millimeters thick; or of rubble stone masonry not less
than 300 millimeters thick. The chimney liner shall be in
accordance with this Code.
(2.2) Masonry Chimneys for Low Heat Appliances —
Masonry chimneys shall be constructed of masonry units
or reinforced concrete with walls not less than 200
millimeters thick: Except, that rubble stone masonry shall
be not less than 300 millimeters thick. The chimney liner
shall be in accordance with this Code.
(2.3) Masonry Chimneys for Medium-Heat Appliances —
Masonry chimneys for medium-heat appliances shall be
constructed of solid masonry units of reinforced concrete
not less than 200 millimeters thick, Except, that stone
masonry shall be not less than 300 millimeters thick and,
in
addition
shall
be
lined
with
not
less
than
100
millimeters of firebrick laid in a solid bed of fire clay
mortar with solidly filled head, bed, and wall joints,
starting not less than 600 millimeters below the chimney
connector entrance. Chimneys extending 7.50 meters or
less above the chimney connector shall be lined to the
top.
(2.4)
Masonry
Chimneys
for
High-Heat Appliances —
Masonry chimneys for high-heat appliances shall be
constructed with double walls of solid masonry units or
reinforced concrete not less than 200 millimeters in
thickness,
with
an
air
space
of
not
less
than
50
millimeters between walls. The inside of the interior walls
shall be of fire-brick not less than 100 millimeters in
thickness laid in a solid bed of fire clay mortar with solidly
filled head, bed, and wall joints.
(2.5)
Masonry Chimneys for Incinerators Installed in
Multi-Storey Buildings (Apartment-Type Incinerators) —
Chimneys
for
incinerators
installed
in
multi-storey
building using the chimney passageway as a refuse chute
where the horizontal grate area of combustion chamber
does not exceed 0.80 square meter shall have walls of
solid masonry or reinforced concrete, not less than 100
millimeters thick with a chimney lining as specified in
this Code. If the grate area of such an incinerator exceeds
0.80 square meter, the walls shall not be less than 100
millimeters of firebrick except that higher than 9.00
meters above the roof of the combustion chamber,
common brick alone 200 millimeters in thickness, may be
used.
(2.6) Masonry Chimneys for Commercial and Industrial
Type Incinerators — Masonry chimneys for commercial
and industrial type incinerators of a size designed for not
more than 110 kilograms of refuse per hour and having a
horizontal grate area not exceeding 0.50 square meter
shall have walls of solid masonry or reinforced concrete
not less than 100 millimeters thick with lining of not less
than 100 millimeters of firebrick, which lining shall extend
for not less than 12.00 meters above the roof of the
combustion chamber. If the design capacity of grate area
of such an incinerator exceeds 110 kilograms per hour and
0.80 square meter respectively, walls shall not be less
than 200 millimeters thick, lined with not less than 100
millimeters of firebrick extending the full height of the
chimney.
(3) Linings — Fire clay chimney lining shall not be less
than 15 millimeters thick. The lining shall extend from 200
millimeters below the lowest inlet, or, in the case of
fireplace, from the throat of the fireplace to a point above
enclosing masonry walls. Fire clay chimney linings shall
be installed ahead of the construction of the chimney as
it is carried up, carefully bedded one on the other in fire
clay mortar, with close-fitting joints left smooth on the
inside. Firebrick not less than 500 millimeters thick may
be used in place of fire clay chimney.
(4) Area — No chimney passageway shall be smaller in
area than the vent connection of the appliance attached
thereto.