(5) Height — Every masonry chimney shall extend at least
600 millimeters above the part of the roof through which
it passes and at least 600 millimeters above the highest
elevation of any part of a building within 3.00 meters to
the chimney.
(6) Corbeling — No masonry chimney shall be corbeled
from a wall more than 150 millimeters nor shall a masonry
chimney be corbeled from a wall which is less than 300
millimeters in thickness unless it projects equally on each
side of the wall. In the second storey of a two-storey
building of Group A Occupancy, corbeling of masonry
chimneys on the exterior of the enclosing walls may equal
the wall thickness. In every case the corbeling shall not
exceed 25 millimeters protection for each course of brick.
(7) Change in Size or Shape — No change in the size or
shape of a masonry chimney shall be made within a
distance of 150 millimeters above or below the roof joints
or rafters where the chimney passes through the roof.
(8) Separation — When more than one passageway is
contained in the same chimney, masonry separation at
least 100 millimeters thick bonded into the masonry wall
of
the
chimney
shall
be
provided
to
separate
passageways.
(9) Inlets — Every inlet to any masonry chimney shall enter
the side thereof and shall be of not less than 3 millimeters
thick metal or 16 millimeters refractory material.
(10) Clearance — Combustible materials shall not be
placed
within
50
millimeters of smoke chamber or
masonry chimney walls when built within a structure, or
within 25 millimeters when the chimney is built entirely
outside the structure.
(11)
Termination
—
All
incinerator
chimneys
shall
terminate in a substantially constructed spark arrester
having a mesh not exceeding 20 millimeters.
(12) Cleanouts — Cleanout openings shall be provided at
the base of every masonry chimney.
(b) Fireplaces and Barbecues — Fireplaces, barbecues,
smoke chambers and fireplace Chimneys shall be of solid
masonry or reinforced concrete and shall conform to the
minimum requirements specified in this Code.
(1) Fireplace Walls — Walls of fireplaces shall not be less
than 200 millimeters in thickness. Walls of fireboxes shall
not be less than 250 millimeters in thickness: Except, that
where a lining of firebrick is used, such walls shall not be
less than 200 millimeters in thickness. The firebox shall
not be less than 200 millimeters in thickness. The firebox
shall not be less than 500 millimeters in depth. The
maximum thickness of joints in firebrick shall be 10
millimeters.
(2) Hoods — Metal hoods used as part of a fireplace or
barbecue shall not be less than No. 18 gauge copper,
galvanized iron, or other equivalent corrosion-resistant
ferrous
metal
with
all
swams
and
connections
of
smokeproof unsoldered construction. The goods shall be
sloped at an angle of 45 degrees or less from the vertical
and shall extend horizontally at least 150 millimeters
beyond the limits of the firebox. Metal hoods shall be kept
a minimum from combustible materials.
(3) Circulators — Approved metal heat circulators may be
installed in fireplaces.
(4) Smoke Chamber — Front and side walls shall not be
less than 200 millimeters in thickness. Smoke chamber
back walls shall not be less than 150 millimeters in
thickness.
(5) Fireplace Chimneys — Walls of chimneys without flue
lining shall not be less than 200 millimeters in thickness.
Walls of chimneys with flue lining shall not be less than
100 millimeters in thickness and shall be constructed in
accordance with the requirements of this Code.
(6) Clearance of Combustible Materials — Combustible
materials shall not be placed within 50 millimeters of
fireplace, smoke chamber, or chimney walls when built
entirely within a structure, or within 25 millimeters when
the
chimney
is
built
entirely
outside
the structure.
Combustible materials shall not be placed within 150
millimeters
of
the
fireplace
opening.
No
such
combustible
material
within
300
millimeters
of
the
fireplace opening shall project more than 3 millimeters
for each 25 millimeters clearance from such opening. No
part of metal hoods used as part of a fireplace, barbecue
or heating stoves shall be less than 400 millimeters from
combustible material. This clearance may be reduced to
the minimum requirements set forth in this Code.
(7) Area of Flues, Throats, and Dampers — The net
cross-sectional area of the flue and of the throat between
the firebox and the smoke chamber of a fireplace shall
not be less than the requirements to be set forth by the
Board. Where dampers are used, they shall be of not less
than No. 12 gauge metal. When fully opened, damper
opening shall be not less than ninety percent of the
required flue area. When fully open, damper blades shall
not extend beyond the line of the inner face of the flue.
(8) Linte — Masonry over the fireplace opening shall be
supported by a non-combustible lintel.
(9) Hearth — Every fireplace shall be provided with a
brick,
concrete,
stone,
or
other
approved
non-combustible hearth slab at least 300 millimeters
wider on each side than the fireplace opening and
projecting at least 450 millimeters therefrom. This slab
shall not be less than 100 millimeters thick and shall be
supported by a non-combustible material or reinforced to
carry its own weight and all imposed loads.
SECTION
1212.
Fire-Extinguishing
Systems .
—
(a)
Fire-Extinguishing Systems — When required, standard
automatic fire-extinguishing systems shall be installed in
the following places, and in the manner provided in this
Code.
(1) In every storey, basement or cellar with an area of 200
square meters or more which is used for habitation,
recreation, dining, study, or work, and which has an
occupant load of more than 20.
(2) In all dressing rooms, rehearsal rooms, workshops or
factories, and other rooms with an occupant load of more
than
10
or
assembly
halls
under
Group
H
and
I
occupancies with occupant load of more than 500, and if
the next doors of said rooms are more than 30.00 meters
from the nearest safe fire dispersal area of the building or
opening to an exit court or street.
(3)
In
all
rooms
used
for
storage
or
handling
of
photographic
x-ray
nitrocellulose
films
and
other
inflammable articles.
(b) Dry Standpipes — Every building four or more storeys
in height shall be equipped with one or more dry
standpipes.
(1) Construction and Tests — Dry standpipes shall be of
wrought iron or galvanized steel and together with
fittings and connections shall be of sufficient strength to
withstand 20 kilograms per square centimeter of water
pressure when ready for service, without leaking at the
joints, valves, or fittings. Tests shall be conducted by the
owner of the building contractor in the presence of a
representative of the Building Official whenever deemed
necessary for the purpose of certification of its proper
function.
(2) Size — Dry standpipes shall be of such size as to be
capable of delivering 900 liters of water per minute from
each of any three outlets simultaneously under the
pressure created by one fire engine or pumper based on
the standard equipment available.
(3) Number Required — Every building four or more
storeys in height where the area of any floor above the
third floor is 950 square meters or less, shall be equipped
with at least one dry standpipes and an additional
standpipe
shall be installed for each additional 950
square meters or fraction thereof.
(4)
Location
—
Standpipes
shall
be
located
within
enclosed stairway landings or near such stairways as
possible or immediately inside of an exterior wall and
within 300 millimeters of an opening in a stairway