enclosure of the balcony or vestibule of a smokeproof
tower or an outside exit stairway.
(5) Siamese Connections — Subject to the provisions of
subparagraph (2) all 100 millimeters dry standpipes shall
be equipped with a two-way Siamese fire department
connection. All 125 millimeter dry standpipes shall be
equipped with a three-way Siamese fire department
connection and 150 millimeters dry standpipes shall be
equipped
with
a
four-way
Siamese fire department
connections.
All
Siamese
inlet
connections
shall
be
located on a street-front of the building and not less than
300 millimeters nor more than 1.20 meters above the
grade and shall be equipped with a clapper-checks and
substantial plugs. All Siamese inlet connections shall be
recessed in the wall or otherwise substantially protected.
(6) Outlets — All dry standpipes shall extend from the
ground floor to and over the roof and shall be equipped
with a 63 millimeters outlet nor more than 1.20 meters
above the floor level at each storey. All dry standpipes
shall be equipped with a two-way 63 millimeters outlet
above the roof. All outlets shall be equipped with gate
valves.
(7) Signs — An iron or bronze sign with raised letters at
least 25 millimeters high shall be rigidly attached to the
building adjacent to all Siamese connections and such
signs shall read "CONNECTION TO DRY STANDPIPE".
(c) Wet Standpipes — Every Group H and I Occupancy of
any height, and every Group C Occupancy of two more
storeys in height and every Group D, D, E, F, and G
Occupancy of three or more storeys in height and every
Group G and E Occupancy over 1800 square meters in
area shall be equipped with one or more interior wet
standpipes extending from the cellar or basement into
the topmost storey: Provided, That Group H buildings
having no stage and having a seating capacity of less
than
500
need
to
be
equipped
with
interior
wet
standpipes.
(1)
Construction
—
Interior
wet
standpipes shall be
constructed of the same materials as those required for
dry standpipes.
(2) Size — (2.1) Interior wet standpipes shall have an
internal diameter sufficient to deliver 190 liters of water
per minute under 2.0 kilograms per square centimeter
pressure at the hose connections. Buildings of Group
Hand I Occupancy shall have wet standpipes systems
capable of delivering the required quantity and pressure
from
any
two
outlets
simultaneously;
for
all
other
occupancies only one outlet need be figured to be
opened at one time. In no case shall the internal diameter
of a wet standpipe be less than 50 millimeters, except
when
the
standpipe
is
attached
to
an
automatic
fire-extinguishing system.
(2.2) Any approved formula which determined pipe sizes
on a pressure drop basis may be used to determine pipe
size for wet standpipe systems. The Building Official may
require
discharge
capacity
and
pressure
tests
on
completed wet standpipe systems.
(3) Number required — The number of wet standpipe
when required in this Code shall be so determined that all
portions of the building are within 6.00 meters of a nozzle
attached to a hose 23.00 meters in length.
(4) Location — In Group H and I Occupancies, outlets shall
be located as follows: one on each side of the stage, one
at the rear of the auditorium and one at the rear of the
balcony. Where occupant loads are less than 500 the
above
requirements
may
be
waived:
Provided, That
portable fire-extinguishers of appropriate capacity and
type are installed within easy access from the said
locations. In Group B, C, D, E, F, and G Occupancies
location
of
all
interior
wet
standpipes
shall
be
in
accordance with the requirement for dry standpipes:
Provided, that at least one standpipe is installed to cover
not more than 650 square meters.
(5)
Outlets
—
All
interior
wet
standpipes
shall
be
equipped with a 38 millimeter valve in each storey,
including the basement or cellar of the building, and
located not less than 300 millimeters nor more than 1.20
meters above the floor.
(6) Threads — All those threads used in connection with
the installation of such standpipes, including valves and
reducing fittings shall be uniform with that prescribed by
the Secretary.
(7) Water Supply — All interior wet standpipes shall be
connected to a street main not less than 100 millimeters
in diameter, or when the water pressure is insufficient, to
a
water
tank
or
sufficient
size
as
provided
in
subparagraph (8). When more than one interior wet
standpipe is required in the building, such standpipe
shall be connected at their bases or at their tops by pipes
of equal size.
(8) Pressure and Gravity Tanks — Tanks shall have a
capacity sufficient to furnish at least 1,500 liters per
minute for period of not less than 10 minutes. Such tanks
shall be located so as to provide not less than 2 kilograms
per sq. cm. pressure at the topmost base outlet for its
entire
supply.
Discharge
pipes
from
pressure
tanks
extend 50 millimeters into and above the bottom of such
tanks. All tanks shall be tested in place after installation
and proved tight at a hydrostatic pressure fifty percent in
excess of the working pressure required. Where such
tanks are used for domestic purposes the supply pipe for
such purposes shall be located at or above the center line
of such tanks. Incombustible supports shall be provided
for all such supply tanks and not less than a 900
millimeters clearance shall be maintained over the top
and under the bottom of all pressure tanks.
(9) Fire pumps — Fire pumps shall have a capacity of not
less than 1,000 liters per minute with a pressure of not
less than 2 kilograms per sq. cm. at the topmost hose
outlet. The source of supply for such pump shall be a
street water main of not less than 100 mm, diameter or a
well or cistern containing a one-hour supply. Such pumps
shall be supplied with an adequate source of power and
shall be automatic in operation.
(10) Hose and Hose Reels — Each hose outlet of all interior
wet standpipe shall be supplied with a hose not less than
38 millimeters in diameter. Such hose shall be equipped
with a suitable brass or bronze nozzle and shall be not
over 23.00 meters in length. An approved standard form
of wall hose reel or rack shall be provided for the hose and
shall be located so as to make the hose readily accessible
at all times and shall be recessed in the walls or protected
by suitable cabinets.
(d) Basement Pipe Inlets — Basement pipe inlets shall be
installed in the first floor of every store, warehouse, or
factory where there are cellars or basements under same:
Except ,
wherein
such
cellars or basements there is
installed a fire-extinguishing system as specified in this
Code or where such cellars or basement are used for
banking purposes, safe deposit vaults, or similar uses.
(1) Material — All basement pipe inlets shall be of cast
iron, steel, brass, or bronze with lids of cast brass or
bronze and shall consist of a sleeve not less than 200
millimeters in diameter through the floor extending to
and flush with the ceiling below and with a top flange,
recessed with an inside shoulder, to receive the lid and
flush with the finished floor surface. The lid shall be a
solid casting and shall have a ring lift recessed on the top
thereof, so as to flushed. The lid shall have the words "FOR
FIRE DEPARTMENT ONLY, DO NOT COVER UP" cast on
the top thereof. The lid shall be installed in such a manner
as to permit its removal readily from the inlet.
(2) Location — Basement pipe inlets shall be strategically
located and kept readily accessible at all times to the Fire
Department.
(e) Approval — All fire-extinguishing systems, including
automatic sprinklers, wet and dry standpipes, automatic
chemical extinguishers, basement pipe inlets, and the
appurtenances thereto shall meet the approval of the fire