COMMERCIAL LAWS SUPPLEMENT
Department as to installation and location and shall be
subject to such periodic test as it may require.
SECTION
1213.
Stages
and
Platform .
—
(a)
Stage
Ventilators — There shall be one or more ventilators
constructed of metal or other incombustible material
near the center and above the highest part of any
working stage raised above the stage roof and having a
total ventilation area equal to at least five percent of the
floor area within the stage walls. The entire equipment
shall conform to the following requirements:
(1) Opening Action — Ventilators shall open by spring
action or force of gravity sufficient to overcome the
effects of neglect, rust, dirt, or expansion by heat or
wrapping of the framework.
(2) Glass — Glass, if used in ventilators must be protected
against falling on the stage. A wire screen, if used under
the glass, must be so placed that if clogged it cannot
reduce the required ventilating area or interfere with the
operating mechanism or obstruct the distribution of
water from the automatic fire extinguishing systems.
(3) Design — Ventilators, penthouses, and supporting
framework shall be designed in accordance with this
Code.
(4)
Spring Actuation — Springs, when employed to
actuate ventilator doors, shall be capable of maintaining
full required tension indefinitely. Springs shall be not
stressed more than fifty percent of their rated capacity
and shall not be located directly in the air stream, nor
exposed to elements.
(5) Location of Fusible Links — A fusible link shall be
placed in the cable control system on the underside of
the ventilator at or above the roof line or as approved by
the Building Official, and shall be so located as not to be
affected by the operation of fire-extinguishing systems.
(6) Control — Remote, manual, or electrical control shall
provide for both opening and closing of the ventilator
doors for periodic testing and shall be located at a point
on the stage designated by the Building Official. When
remote control of ventilator is electrical, power failure
shall not affect its instant operation in the event of fire.
Hand winches may be employed to facilitate operation of
manually controlled ventilators.
(b) Gridirons — (1) Gridirons, fly galleries, and pin-rails shall
be
constructed
of
incombustible
materials
and
fire
protection of steel and iron may be omitted. Gridirons
and fly galleries shall be designed to support a live load of
not less than 367 kilograms per square meter. Each loft
block well shall be designed to support 373 kilograms per
linear meter and the head block well shall be designed to
support the aggregate weight of all the loft block wells
served. The head block well must be provided with an
adequate strengback or lateral brace to offset torque.
(2)
The
main
counterweight
sheave
beam
shall
be
designed to support a horizontal and vertical uniformly
distributed
live
load
sufficient to accommodate the
weight imposed by the total number of loft blocks in the
gridiron.
The
sheave
blocks
shall
be
designed
to
accommodate the maximum load for the loft or head
blocks served with a safety factor of five.
(c) Rooms Accessory to Stage — In a building having a
stage, the dressing room sections, workshops, and store
rooms
shall
be
located
on
the
stage
side
of
the
proscenium wall and shall be separated from each other
and from the stage by not less than a One-hour Fire
Resistive Occupancy Separation.
(d) Proscenium Walls — A stage shall be completely
separated from the auditorium by a proscenium wall or
not less than two-hour incombustible construction. The
proscenium wall shall extend not less than 1.20 meters
above the roof over the auditorium. Proscenium walls
may have the addition to the main proscenium openings,
one opening at the orchestra pit level and not more than
two openings at the stage floor level, each of which shall
be not more than 2.00 square meters in area. All openings
in the proscenium walls of stage shall be protected by a
fire assembly having a one and one-half fire-resistive
rating. The proscenium opening, which shall be the main
opening for viewing performances, shall be provided with
a self closing fire-resistive curtain as specified in this
Code.
(e) Stage Floor — The type of construction for storage
floors shall depend upon the requirements based on the
type of Occupancy and the corresponding fire-resistive
requirements.
All
parts
of
the
stage
floor
shall
be
designed to support not less than 620 kilograms per
square meters. Openings through stage floor shall be
equipped with tight-fitting trap doors of wood of not less
than 5 millimeters nominal thickness.
(f) Platforms — The type of construction for platforms
shall depend upon the requirements based on the type of
Occupancy
and
corresponding
fire-resistive
requirements. Enclosed platforms shall be provided with
one or more ventilators conforming to the requirements
of stage ventilators: Except , that the total area shall be
equal to five percent of the area of the platform. When
more than one ventilator is provided, they shall be so
spaced
as
to
provide
proper
exhaust
ventilation.
Ventilators shall not be required for enclosed platform
having a floor area of 45.00 square meters or less.
(g) Stage Exits — At least one exit not less than 900
millimeters wide shall be provided from each side of the
stage opening directly or by means of a passageway not
less than 900 millimeters in width to a street or exit court.
An exit stair not less than 750 millimeters wide shall be
provided for egress from each fly gallery. Each tier of
dressing rooms shall be provided with at least two means
of egress each not less than 750 millimeters wide and all
such stairs shall be constructed in accordance with the
requirement specified in this Code. The stairs required in
this subsection need not be enclosed.
SECTION 1214. Motion Picture Projection Rooms . — (a)
General — The provisions of this Section shall apply only
where ribbon type motion picture films in excess of
22-millimeters width and electric projection equipment
are used. Every motion picture machine using ribbon
type film in excess of 22 millimeter width and electric arc
projections
equipment,
together
with
all
electrical
devices, rheostats, machines, and all such films present in
any Group C, I, or H Occupancy, shall be enclosed in a
projection room large enough to permit the operator to
walk freely on either side and back of the machine.
(b) Construction — Every projection room shall be of not
less than one-hour fire-resistive construction throughout
and
the
walls
and
ceiling
shall
be
finished
with
incombustible materials. The ceiling shall not be less than
2.40 meters from the finished floor. The room shall have a
floor area of not less than 7.00 square meters and 3.50
square meters for each additional machine.
(c) Exit — Every projection room shall have at least two
doorways separated by not less than one-thirds the
perimeter of the room, each at least 750 millimeters wide
and 2.00 meters high. All entrances to a projection room
shall be protected by a self-closing fire assembly having a
three-fourths hour fire-resistive rating. Such doors shall
open outward and lead to proper exits as required in this
Code and shall not be equipped with any latch. The
maximum width of such door shall be 750 millimeters.
(d) Ports and Openings — Ports in projection room walls
shall be of three kinds: projection ports; observation ports;
and combination ports used for both observation and for
stereopticon, spot or floodlight machines.
(1) Ports Required — There shall be provided for each
motion picture projector not more than one projection
port,
which
shall
be limited in area to 750 square
centimeters, and not more than one observation port,
which shall be limited in area to 1,300 square centimeters.
There shall be not more than three combination ports,
each of which shall not exceed 750 millimeters by 600
millimeters.
Each
port
opening
shall
be
completely
covered with a pane of glass; Except, that when acetate